TRIMOD HE
Double conversion VFI three-phase modular UPS
General specifications
Nominal power (kVA)
10
15
20
30
40
60
Active power (kW)
Module power (kVA)
3.4
5
6.7
Classification
On-Line double conversion VFI-SS-111
System
Modular, expandable and redundant UPS system
Input specifications
Input voltage
380, 400, 415 3PH+N+PE
(or 220, 230, 240 1PH)
Input frequency
45-65 Hz (43,0 ¡À 68.4 Hz)
Input voltage range
400V +15%/-20% - 230V +15%/-20%
400V +15%/-20%
THD input current
‹3% ( at full load)
Compatibility with power supply units
Yes
Input power factor
›0.99
Output Specifications
Output voltage
Efficiency
Up to 96%
Efficiency in Eco mode
99%
Nominal output frequency
50/60 Hz selectable by the user ¡¾2 % (standard), ¡¾14 % (extended)
Crest factor
3:1
Waveform
Sinusoidal
Output voltage tolerance
¡¾1%
THD output voltage
<1%
Permissible overload
10 minutes at 115%, 60 seconds at 135%
Bypass
Automatic bypass (static and electromechanical) and manual maintenance bypass
Batteries
Battery module
Plug & play
Battery series type/voltage
VRLA - AGM / 240 Vdc
Operating time
Configurable
Battery charger
Smart charge technology. 3-stage advanced cycle
Communication and management
Display and signals
4 x 20-character lines, 4 menu navigation buttons,
LED multi-colour status indicator, alarms and audio signals
Communication ports
2 RS232 serial ports, 1 logical gate, 5 ports with dry contacts, 1 slot for interfaces
Backfeed protection
NC/NO auxiliary contact
Emergency Power Off (EPO)
Remote management
Available
Physical Specifications
Height (A-B)
1650 - 1370
1370
Width
414
Depth
628
Installed power modules
3
6
9
Installable battery drawers (A-B)
Up to 16 - Up to 12
Up to 12 - 0
-
Net weight kg (A-B)
155 - 120
181 - 146
146
165
Ambient Conditions
Operating temperature/humidity
0 - 40¡ÆC / 0 - 95% non condensing
Protection rating
IP21
Maximum audible noise at 1 m from the unit (dBA)
46
Conformity
Reference standard
EN 62040-1, EN 62040-2, EN 62040-3