List Pricing |
|
|
|
General |
Topology |
Line-Interactive High Frequency (Pure Sine wave, Buck + Boost) |
Configuration |
Rack/Tower |
Catalog Number |
5PX2200iRT |
Catalog Number Bare |
|
Color |
Black |
Rating (VA/Watts) |
2200/1980 |
Diagnostics |
Full system self-test at power up |
Efficiency |
up to 99%
30
40
50
60
70
80
90
100
86
88
90
92
94
96
98
100
Mouseover graph for detailed efficiency values
|
Dimensions (H x W x D, inches) |
3.4 x 17.4 x 20.6 |
Dimensions (H x W x D, mm) |
86 x 441 x 522 |
Weight (kg) |
29 |
Weight (lbs) |
63 |
Warranty |
3 years on electronics, 3 years on batteries with registration |
Rail Kit Included |
Tower stands and 4-post rail kit included |
Contents (Ships with the following items) |
5PX2200iRT Four-post rail kit User manual CD Tower pedestals Intelligent Power Software Suite CD Quick start guide RS-232 serial cable USB cable 2 IEC to IEC jumper cables Phillips head screw driver |
|
Electrical Input |
Connection |
(1) C20 |
Input Voltage Range |
160–294 Vac (adjustable to 150–294 Vac) |
Nominal Voltage |
230 Vac (adjustable to 200/208/220/230/240 Vac) |
Frequency |
50/60 Hz (auto-sensing) |
Frequency Range |
47–70 Hz (50 Hz system), 56.5–70 Hz (60 Hz system), 40 Hz in low-sensitivity mode |
Input Power Factor |
0.9 |
|
Electrical Output |
Output Receptacles |
(8) C13, (1) C19 |
On Utility Voltage Regulation |
184–265 Vac |
On Battery Voltage Regulation |
-10%, +6% of nominal |
Output Frequency |
50/60 Hz ¡¾0.1 % (autosensing) |
Transfer Time |
1–4 ms typical |
Load Segments |
Group 1: (2) C13 outlets Group 2: (2) C13 outlets view load segments white paper |
|
Battery |
Runtime (minutes)
Load (watts)
250
500
750
1000
1250
1500
1750
0
100
200
300
400
500
600
700
800
|
Standard runtime |
|
with 1 EBM |
|
with 2 EBMs |
|
with 3 EBMs |
|
with 4 EBMs |
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc. |
Optional Extended Battery Module |
5PXEBM48RT |
Battery Management |
ABM¢ç technology and temperature-compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of extended battery modules (EBMs) |
Battery Type |
12V/9 Ah; sealed, lead-acid; maintenance free |
Battery Replacement |
Hot-swappable internal batteries and extended battery modules (EBMs) |
Start On Battery |
Allows start of UPS without utility power |
|
Communications |
User Interface |
LCD graphical display |
LEDs |
Load Protected, Battery, and Fault |
Communication Ports |
1 USB HID compliant port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously) |
Communications Card Slots |
1 slot for ConnectUPS-MS network management card |
Power Management Software |
Eaton Intelligent Power Software Suite CD (included) |
|
Environmental & Standards |
Heat Dissipation (BTU) |
Line: 305, Battery: 2047 |
Audible Noise |
<45 dBA |
Operating Temperature |
0¡ÆC–40¡ÆC (32¡ÆF–104¡ÆF) |
Performance - Safety - EMC |
IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (Performance) |
Safety markings |
CE, CB report, TÜV, C-Tick |
Storage Temperature |
-15¡ÆC–50¡ÆC (5¡ÆF–122¡ÆF) |
Relative Humidity |
20–95% non-condensing |
Altitude |
Up to 10,000 ft (3000m) without de-rating |
|
|